At a Glance

Cut Sheets

p> While a Remote Hazard Indicator is required in the area served by an isolated power system, it is often convenient to know the status of the isolating system as each device is energized within the operating room.

The Remote Hazard Indicator with Meter contains a micro ammeter, which duplicates the meter in the Line Isolation Monitor located within the Isolated Power Center.

When leakage current is within the safe range for the isolation systems being monitored, a steady green indicator light will show that the system is in a SAFE condition. When a total hazard index [leakage current to ground] is exceeded, the green light will extinguish and a red HAZARD indicator light will be illuminated; additionally an audible alarm will call attention to the potential hazard. The audible alarm may be silenced by pressing a momentary pushbutton. A yellow SILENCED indicator will be illuminated to show that the alarm is silenced. When the leakage current is again within the acceptable range, the remote hazard indicator will automatically return to the SAFE condition and reset the audible alarm.

The Remote Hazard Indicator is of solid state, compact, robust construction for long life. The indicator lamps are replaceable from the front without the removal of the unit from the wall. The Remote Hazard Indicator is mounted on a standard, three-gang, stainless steel faceplate, and will mount in a standard three-gang electrical box. The electrical box is not provided.

Ordering Information:

Compatible with
Line Isolation Monitor
Part Number Plate
Size
LEA [Analog] 358383 4-gang
LBA [Analog] 358683 3-gang
LE [Analog/Digital] 358908 4-gang
LB [Digital] N/A